HRN EN 50525-2-31 - EN 50525-2-31 - IEC 60227-3
Insulation PVC compound TI1 acc. to EN 50363-3
Flexible insulated conductor for wiring within electrical devices, lighting fixtures, switchingand distribution boxes, i.e. as bridge junction. Laid in dry areas, in closed electricalinstallation conduits only for signaling and control circuits. Not for direct application under plaster.
Equivalents:
P/F acc. to HRN N.C3.202
227 IEC 01 acc. to IEC 60227-3
Ysf acc. to ÖVE / ÖNORM E 8241(HD21)
Standards:
HRN EN 50525-2-31
EN 50525-2-31
IEC 60227-3
Nominal voltage: U0/U = 300/500 V
Test voltage: 2000 V
Temperature range:
Minimum temperatureduring installation: +5 C
Fixed installed: -30 C do +80 C
At short circuit of max. 5s: 160 C
Behaviour in fire:
Flame retardant (self-extinguishing) cable acc. to
EN 60332-1-2
Minimal inner bending radius: 12,5xØ cable
CONSTRUCTION DATA | |||||
Construction |
Outer |
Conductor |
Cu weight |
Cable |
Packing* |
mm2 | ca. mm | Ω/km | kg/km | ca. kg/km | |
1 X 0,5 | 2,1 | 39 | 4,8 | 8 | KOT 100 |
1 X 0,75 | 2,4 | 26 | 7,2 | 11 | KOT 100 |
1 X 1 | 2,5 | 19,5 | 9,6 | 14 | KOT 100 |
(y/g) yellow-green
(bl) blue
(bn) brown
(bk) black
(gy) grey
(rd) red
(vi) violet
(or) orange
(wh) white
(db) dark blue
(ye) yellow
(gn) green
*Packing: KOT 100 = coil 100m