NYY
PVC insulated and sheathed power cable
HRN HD 603 S1 - DIN VDE 0276-603 - IEC 60502-1

cable conforms to Low voltage directive max. permitted conductor temperature min. installation temperature flame retardant acc. IEC 60332-1 UV resistant cable cable for direct burial
CONSTRUCTION
Conductor    Cu class 1 or 2 acc. to EN 60228
a) Class1:    solid, round (RE)
b) Class2:    multi wire stranded, round (RM)

Insulation   PVC compound DIV-4 acc. to HD 603.1

Filler   extruded elastomer or plastomer compound
Sheath   PVC compound DMV-5, acc.to HD 603.1
APPLICATION

Distribution and signal power cable for static outdoor application (with protection against direct UV-irradiation), in ground, within facilities, in cable canals, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are not expected. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and in other electric plants, same as for connection of signalling devices in industry, traffic and similar.
 

 TECHNICAL DATA

Equivalents:
PP00 acc. to IEC 60502-1
EYY acc. to ÖVE-K 603 

Standards: 
HRN HD 603 S1 
DIN VDE 0276-603 
IEC 60502-1 

Nominal voltage: U0/U = 0,6/1 kV
Test voltage: 4 kV

Temperature range:
Minimum temperature during installation: -5° C
Fixed installed: -20° C to +70° C
At short circuit of max. 5s: 160° C

Behaviour in fire:
Flame retardant (self-extinguishing) cable
acc. to EN 60332-1-2

Minimal inner bending radius: 12xØ multi core,
15xØ single core

CONSTRUCTION DATA
Construction Shape
of the
conductor
Outer
diameter
Conductor
resistance
at 20 °C
Current
carrying
capacity (air)
Current
carrying
capacity (ground)
Cu
weight
Cable
weight
Packing*
mm2   ca. mm Ω/km nom.A nom.A kg/km ca. kg/km  
1 X 4 RE 7,9 4,61 37 50 38,4 110 KOT 100, SP40 500
1 X 6 RE 8,4 3,08 47 62 57,6 130 KOT 100, SP40 500
1 X 10 RE/RM 9,3 1,83 64 83 96 180 SP45 500
1 X 16 RE/RM 10,7 1,15 84 107 153,6 240 SP45 500, SP50 500
1 X 25 RE 12,5 0,727 114 138 240 350 SP60 500
1 X 35 RE 13,6 0,524 139 164 336 460 SP60 500
1 X 50 RE 15,4 0,387 169 195 480 600 SP70 500
2 X 1,5 RE 11,6 12,1 20 27 28,8 190 SP45 500
2 X 2,5 RE 12,4 7,41 25 36 48 230 SP50 500
2 X 4 RE 14,1 4,61 34 47 76,8 310 SP60 500
2 X 6 RE 15,1 3,08 43 59 115,2 380 SP60 500
3 X 1,5 RE 12,0 12,1 20 27 43,2 190 KOT 100, SP50 500
3 X 2,5 RE 12,9 7,41 25 36 72 240 KOT 100, SP50 500
3 X 4 RE 14,8 4,61 34 47 115,2 330 KOT 100, SP60 500
3 X 6 RE 15,9 3,08 43 59 178,8 420 SP70 500
3 X 10 RE/RM 18,1 1,83 59 79 288 580 DB08 500
3 X 16 RE/RM 21,0 1,15 79 102 460,8 810 DB08 500
3 X 25 RE 25,1 0,727 106 133 720 1300 DB10 500
3 X 35 RE 27,5 0,524 129 159 1008 1400 DB10 500
4 X 1,5 RE 13,0 12,1 20 27 57,6 230 KOT 100, SP50 500
4 X 2,5 RE 13,9 7,41 25 36 96 290 KOT 100, SP60 500
4 X 4 RE 15,8 4,61 34 47 153,6 400 KOT 100, SP70 500
4 X 6 RE 16,9 6,08 43 59 230,4 510 DB08 500
4 X 10 RE/RM 19,1 1,83 59 79 384 720 DB08 500
4 X 16 RE/RM 22,0 1,15 79 102 614,4 1050 DB09 500
4 X 25 RE 27,8 0,727 106 133 960 1600 DB10 500
5 X 1,5 RE 13,3 12,1 20 27 72 270 KOT 100, SP60 500
5 X 2,5 RE 14,3 7,41 25 36 120 350 KOT 100, SP60 500
5 X 4 RE 16,7 4,61 34 47 192 480 DB08 500
5 X 6 RE 18,1 3,08 43 59 288 610 DB08 500
5 X 10 RE/RM 21,5 1,83 59 79 480 880 DB09 500
5 X 16 RE/RM 25,7 1,15 79 102 768 1250 DB10 500
 
 
Sheath colour identification

(bk) black

* Packing: KOT 100 = coil 100m, SP = cable on plywood reel, DB = cable on wooden drum

PDF Download       VDE certificate        DoP