EYY
PVC insulated and sheathed power cable
HRN HD 603 S1 - ÖVE-K 603 - IEC 60502-1

cable conforms to Low voltage directive max. permitted conductor temperature min. installation temperature flame retardant acc. IEC 60332-1 UV resistant cable cable for direct burial
CONSTRUCTION
Conductor    Cu class 1 or 2 acc. to EN 60228
a) Class1:    solid, round (RE)
b) Class2:    multi wire stranded, round (RM)
Insulation    PVC compound DIV-1 acc. to HD 603.1
Filler    extruded elastomer or plastomer compound
Sheath     PVC compound DMV-1 acc. to HD 603.1
APPLICATION

Distribution and signal power cable for static outdoor application (with protection against direct UV-irradiation), in ground, within facilities, in cable canals, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are not expected. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and in other electric plants, same as for connection of signalling devices in industry, traffic and similar.
 

 TECHNICAL DATA

Equivalents:
PP00 acc. to HRN N.C5 220
NYY acc. to DIN VDE 0276-603

Standards: 
HRN HD 603 S1 
ÖVE-K 603
IEC 60502-1

Nominal voltage: U0/U = 0,6/1 kV
Test voltage: 4 kV

Temperature range:
Minimum temperature during installation: -5° C
Fixed installed: -20° C to +70° C
At short circuit of max. 5s: 160° C

Behaviour in fire:
Flame retardant (self-extinguishing) cable
acc. to EN 60332-1-2

Minimal inner bending radius: 12xØ multi core,
 15xØ single core

CONSTRUCTION DATA
Construction

Shape
of the
conductor

Outer
diameter

Conductor
resistance
at 20 °C

Current
carrying
capacity (air)

Current
carrying
capacity (ground)

Cu
weight

Cable
weight

Packing*
mm2   ca. mm Ω/km nom.A nom.A kg/km ca. kg/km  
1 X 4 RE 7,5 4,61 37 50 40 85 KOT 100, SP40 500
1 X 6 RE 8,0 3,08 47 62 60 111 KOT 100, SP40 500
1 X 10 RE/RM 9,3 1,83 64 83 100 164 SP45 500
1 X 16 RE/RM 10,3 1,15 84 107 160 228 SP45 500, SP60 500
1 X 25 RM 12,1 0,727 114 138 250 336 SP60 500
1 X 35 RM 13,2 0,524 139 164 350 445 SP60 500
1 X 50 RM 15,0 0,387 169 195 500 598 SP70 500
2 X 1,5 RE 11,4 12,1 20 27 30 184 SP45 500
2 X 2,5 RE 12,2 7,41 25 36 50 218 SP50 500
2 X 4 RE 13,7 4,61 34 47 80 300 SP60 500
2 X 6 RE 14,7 3,08 43 59 120 348 SP60 500
3 X 1,5 RE 11,8 12,1 20 27 45 201 KOT 100, SP50 500
3 X 2,5 RE 12,7 7,41 25 36 75 243 KOT 100, SP50 500
3 X 4 RE 14,4 4,61 34 47 120 342 KOT 100, SP60 500
3 X 6 RE 15,5 3,08 43 59 180 425 SP70 500
3 X 10 RE/RM 17,2 1,83 59 79 300 594 DB08 500
3 X 16 RE/RM 20,6 1,15 79 102 480 835 DB08 500
3 X 25 RM 24,7 0,727 106 133 750 1180 DB10 500
3 X 35 RM 27,1 0,524 129 159 1050 1460 DB10 500
4 X 1,5 RE 12,6 12,1 20 27 60 204 KOT 100, SP50 500
4 X 2,5 RE 13,5 7,41 25 36 100 274 KOT 100, SP60 500
4 X 4 RE 15,4 4,61 34 47 160 378 KOT 100, SP70 500
4 X 6 RE 16,5 3,08 43 59 240 482 DB08 500
4 X 10 RE/RM 18,8 1,83 59 79 400 689 DB08 500
4 X 16 RE/RM 21,6 1,15 79 102 640 986 DB09 500
4 X 25 RM 27,4 0,727 106 133 1000 1420 DB10 500
5 X 1,5 RE 13,0 12,1 20 27 75 239 KOT 100, SP60 500
5 X 2,5 RE 13,9 7,41 25 36 125 306 KOT 100, SP60 500
5 X 4 RE 16,2 4,61 34 47 200 418 DB08 500
5 X 6 RE 17,7 3,08 43 59 300 564 DB09 500
5 X 10 RE/RM 20,2 1,83 59 79 500 854 DB09 500
5 X 16 RE/RM 25,5 1,15 79 102 800 1205 DB10 500
 
 
Sheath colour identification

(bk) black

* Packing: KOT 100 = coil 100m, SP = cable on plywood reel, DB = cable on wooden drum

PDF Download      ÖVE certificate       DoP