NY2Y
PVC insulated and sheathed power cable
HRN HD 603 S1 - DIN VDE 0276-603 - IEC 60502

cable conforms to Low voltage directive max. permitted conductor temperature min. installation temperature flame retardant acc. IEC 60332-1 UV resistant cable cable for direct burial
CONSTRUCTION
Conductor    Cu, class 1 or 2 acc. to EN 60228
a) Class 1:    solid, round(RE)
b) Class 2:    multi wire stranded, round (RM)

Insulation   PVC compound DIV-4 acc. to HD 603 S1-1

Filler  extruded elastomer or plastomer compound
Sheath    PE (polyethylene) compound DMP 2 acc. to HD 603 S1-1
APPLICATION

Distribution power cable for static outdoor applicatio, in ground, within facilities, in cable canals, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are expected. The advantage of this cable is in the hardness of HDPE outer shell, so it can be used in an environment where greater mechanical damage can be expected.
 

 TECHNICAL DATA

Equivalents:
E-Y2Y acc. to ÖVE-K 603

Standards: 
HRN HD 603 S1 
DIN VDE 0276-603
IEC 60502

Nominal voltage: U0/U = 0,6/1 kV
Test voltage: 4 kV

Temperature range:
Minimum temperature during installation: -5° C
Fixed installed: -20° C to +70° C
At short circuit of max. 5s: 160° C

Behaviour in fire:
Flame retardant (self-extinguishing) cable
acc. to EN 60332-1-2

Minimal inner bending radius: 12xØ multi core,
15xØ single core

CONSTRUCTION DATA
Construction

Shape
of the
conductor

Outer
diameter

Conductor
resistance
at 20 °C

Current
carrying
capacity (air)

Current
carrying
capacity (ground

Cu
weight

Cable
weight

Packing*
mm2   ca. mm Ω/km nom.A nom.A kg/km ca. kg/km  
1 X 10 RE/RM 9,1 1,83 81 124 96 162 SP45 500
1 X 16 RE/RM 10,7 1,15 107 160 153,6 218 SP45 500
1 X 25 RE 12,5 0,727 144 208 240 338 SP50 500
1 X 35 RE 13,6 0,524 176 250 336 442 SP60 500
1 X 50 RE 15,4 0,387 214 296 480 573 SP70 500
2 X 1,5 RE 11,6 12,1 22 34 28,8 125 SP45 500
2 X 2,5 RE 12,4 7,41 30 45 48 161 SP50 500
2 X 4 RE 14,1 4,61 40 59 76,8 230 SP60 500
2 X 6 RE 15,1 3,08 51 73 115,2 305 SP60 500
3 X 1,5 RE 12,0 12,1 19 27 43,2 140 KOT 100, SP50 500
3 X 2,5 RE 12,9 7,41 25 36 72 186 KOT 100, SP50 500
3 X 4 RE 14,8 4,61 34 46 115,2 256 KOT 100, SP60 500
3 X 6 RE 15,9 3,08 43 58 172,8 354 SP70 500
3 X 10 RE/RM 17,6 1,83 59 78 288 520 DB09 500
3 X 16 RE/RM 21,0 1,15 78 101 460,8 768 DB09 500
3 X 25 RE 25,1 0,727 105 132 720 1196 DB10 500
3 X 35 RE 27,5 0,524 129 159 1008 1525 DB12 500
4 X 1,5 RE 13,0 12,1 19 27 57,6 165 KOT 100, SP50 500
4 X 2,5 RE 13,9 7,41 25 36 96 225 KOT 100, SP60 500
4 X 4 RE 15,8 4,61 34 46 153,6 326 KOT 100, SP70 500
4 X 6 RE 16,9 3,08 43 58 230,4 436 SP75 500
4 X 10 RE/RM 19,1 1,83 59 78 384 620 DB09 500
4 X 16 RE/RM 22,0 1,15 78 107 614,4 980 DB10 500
4 X 25 RE 27,8 0,727 105 132 960 1506 DB12 500
5 X 1,5 RE 13,3 12,1 19 27 72 192 KOT 100, SP60 500
5 X 2,5 RE 14,3 7,41 25 36 120 264 KOT 100, SP60 500
5 X 4 RE 16,7 4,61 34 46 192 369 KOT 100, SP75 500
5 X 6 RE 18,1 3,08 43 58 288 518 DB09 500
5 X 10 RE/RM 20,6 1,83 597 78 480 780 DB09 500
5 X 16 RE/RM 25,7 1,15 8 101 768 1198 DB10 500
 
 
Sheath colour identification

(bk) black

* Packing: KOT 100 = coil 100m, SP = cable on plywood reel, DB = cable on wooden drum

PDF Download