HRN EN 50525-2-31 - EN 50525-2-31 - IEC 60227-3
Insulation PVC compound TI1 acc. to EN 50363-3
Insulated conductor is used for laying in electric-installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment, same as for protective laying for lighting of nominal voltage up to 750 V alternating current.
Equivalents:
P acc. to HRN N.C3.200
227 IEC 01 acc. to IEC 60227-3
Ye acc. to ÖVE / ÖNORM E 8241
Standards:
HRN EN 50525-2-31
EN 50525-2-31
IEC 60227-3
Nominal voltage:U0/U = 450/750 V
Test voltage:2500 V
Temperature range:
Minimum temperature during installation: +5 C
Fixed installed: -30 C do +80 C
At short circuit of max. 5s: 160 C
Behaviour in fire:
Flame retardant (self-extinguishing) acc. EN 60332-1-2
Minimal inner bending radius: 12,5xØ cable
CONSTRUCTION DATA | |||||
Construction | Outer dimeter |
Conductor resistance at 20°C |
Cu weight |
Cable weight |
Packing* |
mm2 | ca. mm | Ω/km | kg/km | ca. kg/km | |
1 X 1,5 | 2,8 | 12,1 | 14,4 | 20 | KOT 100, SP40 4000 |
1 X 2,5 | 3,4 | 7,41 | 24 | 31 | KOT 100, SP40 4000 |
1 X 4 | 3,9 | 4,61 | 38,4 | 46 | KOT 100 |
1 X 6 | 4,3 | 3,08 | 57,6 | 65 | KOT 100, SP40 500 |
1 X 10 | 5,5 | 1,83 | 96 | 110 | KOT 100 |
(y/g) yellow-green
(bl) blue
(bn) brown
(bk) black
(gy) grey
(rd) red
(vi) violet
(or) orange
(wh) white
(db) dark blue
(ye) yellow
(gn) green
* Packing: KOT 100 = coil 100m, SP = cable on plywood reel