NHXMH
Halogen free installation cable 300/500V
DIN VDE 0250-214

cable conforms to Low voltage directive halogen-free cable low smoke emission cable max. permitted conductor temperature min. installation temperature flame retardant acc. IEC 60332-3
CONSTRUCTION
Conductor   bare copper conductor class1 or class 2, acc. to EN 60228

Insulation   cross-linked polymer, type 2XI1 acc. to HD 604 S1 / DIN VDE 0276-604

Filler     HFFR extruded halogen-free polymer

Sheath    HFFR extruded halogen-free polymer type HM2 acc. to DIN VDE 0250-214
APPLICATION

Halogen-free installation cable suitable for application in household and industry, in facilities where human lives or valuable property need to be protected against damages caused by fire. Used as halogen-free alternative to NYM cable. Recommended for public buildings frequented by a lot of people, and for buildings of high material value, for industrial complexes, electric power plants, transformer stations, municipal facilities, hotels, shopping malls, hospitals, schools, airports, underground railways and similar. Laid in, on or under plaster, in walls or in concrete, directly or in cable canals, without special mechanical protection, but not in dry or prestressed concrete. Suitable for dry, damp or wet environment, for internal or outdoor application (only if the cable is protected against direct sunlight). Advantages: halogen-free, no release of toxic or corrosive gases under fire, reduced smoke occurrence under fire, no flame propagation in vertical cable bundle.
 

 TECHNICAL DATA


Standards:
DIN VDE 0250-204 


Nominal voltage: U0/U = 300/500 V
Test voltage: 2000 V

Temperature range:
Minimum temperature during installation: +5 C
Fixed installed: -20 C do +70 C
At short circuit of max. 5s: 160 C

Behaviour in fire:
EN 60332-3

Minimal inner bending radius: 10xØ multi core,
15xØ single core

CONSTRUCTION DATA
Construction

Outer
diameter

Conductor
resistance
at 20 °C

Cu
weight

Cable
weight

Packing*
mm2 ca. mm Ω/km kg/km ca. kg/km  
1 X 1,5 5,3 12,1 14,4 40 KOT 100, SP40 500
1 X 2,5 5,7 7,41 24 55 KOT 100, SP40 500
1 X 4 6,4 4,61 38,4 74 KOT 100, SP40 500
1 X 6 6,8 3,08 57,6 105 KOT 100, SP40 500
1 X 10 7,9 1,83 96 155 KOT 100, SP40 500
1 X 16 9,0 1,15 153,6 230 KOT 100, SP45 500
2 X 1,5 8,3 12,1 28,8 115 KOT 100, SP40 500
2 X 2,5 9,1 7,41 48 190 KOT 100, SP45 500
2 X 4 10,5 4,61 76,8 195 KOT 100, SP50 500 
3 X 1,5 8,7 12,1 43,2 135 KOT 100, SP40 500
3 X 2,5 9,5 7,41 72 190 KOT 100, SP45 500
3 X 4 11,0 4,61 115,2 265 KOT 100, SP50 500
3 X 6 12,5 3,08 172,8 315 KOT 100, SP60 500
3 X 10 15,8 1,83 288 465 KOT 100, DB08 500
4 X 1,5 9,3 12,1 57,6 160 KOT 100, SP45 500
4 X 2,5 10,2 7,41 96 230 KOT 100, SP50 500
4 X 4 12,3 4,61 153,6 330 KOT 100, SP60 500
4 X 6 13,9 3,08 230,4 460 KOT 100, DB08 500
4 X 10 17,3 1,83 384 690 DB08 500
4 X 16 20,5 1,15 614,4 1090 DB09 500
5 X 1,5 10,0 12,1 72 190 KOT 100, SP45 500
5 X 2,5 11,0 7,41 120 270 KOT 100, SP60 500
5 X 4 13,7 4,61 192 410 KOT 100, DB08 500
5 X 6 15,0 3,08 288 540 KOT 100, DB08 500
5 X 10 18,8 1,83 480 870 DB09 500
5 X 16 22,8 1,15 768 1350 DB10 500
7 X 1,5 10,9 12,1 100,8 235 KOT 100, SP50 500
7 X 2,5 12,3 7,41 168 350 KOT 100, SP50 500
 
 
Sheath colour identification

(gy) grey

*Packing: KOT 100 = coil 100m, SP = cable on plywood reel, DB = cable on wooden drum

 PDF Download