NYM
PVC insulated and sheathed installation cable
HRN HD 21.4 S2 - DIN VDE 0250-204 - IEC 60227-4

VDE-certified cabel cable conforms to Low voltage directive max. permitted conductor temperature min. installation temperature flame retardant acc. IEC 60332-1
CONSTRUCTION
Conductor    bare copper conductor class1 or class 2, acc. to EN 60228

Insulation    PVC compound TI1 acc. to EN 50363-3

Filler   cores enveloped in non-vulcanized rubber or plastic compound

Sheath    PVC compound TM1 acc. to EN 50363-4-1
APPLICATION

Installation cable suitable for household and industrial usage. Laid on or under plaster, in walls or concrete, without special mechanical protection, but not in dry or pre-stressed concrete. Suitable for dry, same as damp or wet environment; for indoor or outdoor application (only if the cable is protected against direct sunlight).
 

 TECHNICAL DATA


Equivalents:
PP acc. to HRN N.C3.200 
A05VV-U, A05VV-R acc. to HRN HD 21.4 S2 
YM acc. to ÖVE-K 41-4

Standards: 
HRN HD 21.4 S2
DIN VDE 0250-204 
IEC 60227-4


Nominal voltage: U0/U = 300/500 V
Test voltage: 2000 V

Temperature range:
Minimum temperature during installation: +5 C
Fixed installed: -20 C do +70 C
At short circuit of max. 5s: 160 C

Behaviour in fire:
Flame retardant (self-extinguishing) cable
acc. to EN 60332-1-2

Minimal inner bending radius: 4xØ cable

CONSTRUCTION DATA
Construction

Outer
diameter

Conductor
resistance
at 20 °C

Cu
weight

Cable
weight

Packing*
mm2 ca. mm Ω/km kg/km ca. kg/km  
1 X 6 7,3 3,08 57,6 105 KOT 100, SP40 500
1 X 10 8,5 1,83 96 155 KOT 100, SP40 500
1 X 16 9,8 1,15 153,6 230 KOT 100, SP45 500 
2 X 1,5 8,5 12,1 28,8 105 KOT 100, SP40 500
2 X 2,5 9,8 7,41 48 134 KOT 100, SP45 500
3 X 1,5 8,9 12,1 43,2 123 KOT 100, SP40 500
3 X 2,5 10,4 7,41 72 176 KOT 100, SP45 500
3 X 4 12,0 4,61 115,2 248 KOT 100, SP50 500
3 X 6 14,8 3,08 182,8 342 KOT 100, SP60 500
3 X 10 17,7 1,83 288 585 KOT 100, DB08 500
3 X 16 19,2 1,15 460,8 790 DB09 500
4 X 1,5 9,6 12,1 57,6 144 KOT 100, SP45 500
4 X 2,5 11,3 7,41 96 212 KOT 100, SP50 500
4 X 4 13,0 4,61 153,6 302 KOT 100, SP60 500
4 X 6 14,9 3,08 230,4 416 KOT 100, DB08 500
4 X 10 19,4 1,83 384 715 DB08 500
4 X 16 21,9 1,15 614,4 987 DB09 500
5 X 1,5 10,5 12,1 72 173 KOT 100, SP40 500
5 X 2,5 12,3 7,41 120 256 KOT 100, SP60 500
5 X 4 14,2 4,61 192 363 KOT 100, DB08 500
5 X 6 16,2 3,08 288 506 KOT 100, DB08 4000
5 X 10 21,2 1,83 480 874 DB09 500
5 X 16 24,0 1,15 768 1213 DB10 500
7 X 1,5 11,6 12,1 100,8 208 KOT 100, SP50 500
7 X 2,5 13,1 7,41 168 325 KOT 100, SP50 500
 
 
Sheath colour identification

(gy) grey

*Packing: KOT 100 = coil 100m, SP = cable on plywood reel, DB = cable on wooden drum

 PDF Download      VDE certificate       DoP