HRN EN 50525-2-31 - EN 50525-2-31 - IEC 60227-3
Insulation PVC compound TI1 acc.to EN 50363-3
Insulated conductor used for laying in electricinstallation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment, same as for protective laying for lighting of nominal voltage up to 750 V alternating current.
Equivalents:
P/M acc. to HRN N.C3.201
227 IEC 01 acc. to IEC 60227-3
Ym acc. to ÖVE / ÖNORM E 8241
Standards::
HRN EN 50525-2-31
EN 50525-2-31
IEC 60227-3
Nominal voltage: U0/U = 450/750 V
Test voltage: 2500 V
Temperature range:
Minimum temperature during installation: +5 C
Fixed installed: -30 C do +80 C
At short circuit of max. 5s: 160 C
Behaviour in fire:
Flame retardant (self-extinguishing) cable
acc. toEN 60332-1-2
Minimal inner bending radius: 12,5xØ cable
CONSTRUCTION DATA | |||||
Construction | Outer diameter |
Conductor resistance at 20°C |
Cu weight |
Cable weight |
Packing* |
mm2 | ca. mm | Ω/km | kg/km | ca. kg/km | |
1 X 10 | 6,1 | 1,83 | 96 | 120 | KOT 100, SP40 500 |
1 X 16 | 7,1 | 1,15 | 153,6 | 175 | KOT 100, SP40 500 |
1 X 25 | 8,9 | 0,727 | 240 | 275 | SP40 500 |
1 X 35 | 10 | 0,524 | 336 | 370 | SP45 500 |
1 X 50 | 10,7 | 0,387 | 480 | 500 | SP50 500 |
(y/g) yellow-green
(bl) blue
(bn) brown
(bk) black
(gy)grey
* Packing: KOT 100 = coil 100m, SP = cable on plywood reel