H07V-R
PVC insulated conductor - multi wire
HRN EN 50525-2-31 - EN 50525-2-31 - IEC 60227-3

VDE-certified cable cable conforms to Low voltage directive max. permitted conductor temperature min. installation temperature flame retardant acc. IEC 60332-1
CONSTRUCTION
Conductor  bare copper conductor class1 or class 2, acc. to EN 60228

Insulation  PVC compound TI1 acc.to EN 50363-3

 

 

APPLICATION

Insulated conductor used for laying in electricinstallation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment, same as for protective laying for lighting of nominal voltage up to 750 V alternating current.
 

 TECHNICAL DATA


Equivalents:
P/M acc. to HRN N.C3.201
227 IEC 01 acc. to IEC 60227-3
Ym acc. to ÖVE / ÖNORM E 8241

Standards::
HRN EN 50525-2-31
EN 50525-2-31
IEC 60227-3


Nominal voltage: U0/U = 450/750 V
Test voltage: 2500 V

Temperature range:
Minimum temperature during installation: +5 C
Fixed installed: -30 C do +80 C
At short circuit of max. 5s: 160 C

Behaviour in fire:
Flame retardant (self-extinguishing) cable
acc. to
EN 60332-1-2


Minimal inner bending radius: 12,5xØ cable

CONSTRUCTION DATA
Construction Outer
diameter
Conductor resistance
at 20°C
Cu
weight
Cable
weight
Packing*
mm2 ca. mm Ω/km kg/km ca. kg/km  
1 X 10 6,1 1,83 96 120 KOT 100, SP40 500
1 X 16 7,1 1,15 153,6 175 KOT 100, SP40 500
1 X 25 8,9 0,727 240 275 SP40 500
1 X 35 10 0,524 336 370 SP45 500
1 X 50 10,7 0,387 480 500 SP50 500
 
 
Conductor colour identification

(y/g) yellow-green
(bl) blue
(bn) brown
(bk) black
(gy)grey

 

* Packing: KOT 100 = coil 100m, SP = cable on plywood reel

 PDF Download      VDE certificate       ÖVE certificate        DoP